System design for energy efficient pump operation in buildings
Panel: 6. Innovations in buildings and appliances
This is a peer-reviewed paper.
Author:
Caroline Markusson, Building Services Engineering, Chalmers University of Technology, Sweden
Lennart Jagemar, CIT Energy Management, Sweden
Per Fahlén, Building Services Engineering, Sweden
Abstract
In this study the use of decentralized pumps in heating systems are investigated from a design and control perspective. In a decentralized pump system the centralized pump, control valves and balancing valves of the traditional system is replaced by individually controlled pumps. The energy saving potential (heat and electric) as well as pros and cons of decentralized systems are investigated. A radiator system of twenty radiators situated in a typical Swedish office building located in Gothenburg is used as a case study. In traditional radiator heating systems the heating capacity is controlled by a variable temperature. The temperature on the secondary side of the system is obtained by mixing supply and return water to desired inlet temperature. A more energy efficient way is heating capacity control by variable flow rate. The pump power is proportional to the cube of the flow rate and accordingly the pump power will decrease substantially at reduced heating capacities. Flow rate control can be achieved by using a 2-way valve or decentralized variable speed pumps. Furthermore, in direct flow control systems the control valve can be removed and as a consequence the pump power at the design flow rate is at least half. Advantages with decentralized pump systems, apart from reduced pump power, include individual demand control based on the required room temperatures and increased possibilities for optimization of heat energy and pump work without extra penalty in pump work. A further advantage is that no balancing of the system is required. The main disadvantages include wiring for pumps and controllers. Results from the case study indicate a saving in pump energy of 60 % and heat energy of almost 50 %. For an analysis period of 10 years and a real interest rate of 5 % the allowed investment (present value of the annual energy savings) for the decentralized system in this case study is € 530 per radiator.
Downloads
Download this presentation as pdf: 6-365_Markusson_pre.pdf
Download this paper as pdf: 6-365_Markusson.pdf