Laboratory testing of residential heat pump controllers for demand response using pricing profiles
Panel: 8. Buildings: technologies and systems beyond energy efficiency
This is a peer-reviewed paper.
Authors:
Ammi Amarnath, Electric Power Research Institute, USA
Don Shirey, Electric Power Research Institute, USA
Alekhya Vaddiraj, Electric Power Research Institute, USA
Thibault Pean, Institut de Rercerca en Energia de Catalunya - IREC, Spain
Jaume Salom, Institut de Rercerca en Energia de Catalunya - IREC, Spain
Abstract
The modern power system needs to be increasingly flexible to efficiently integrate abundant intermittent renewable energy within a complex network comprising a growing number of distributed energy resources (DERs) and electrical loads.
A cost-effective approach to provide grid flexibility is the adjustment of demand-side electric consumption profiles. In European Union (EU) households 79% of total energy use is due to space conditioning and domestic water heating, so residential heat pumps can play a major role for providing flexibility to energy grids.
A residential water-to-air heat pump was evaluated in a laboratory setting to quantify electric load flexibility when controlled based on demand response (DR) curtailment signals and day-ahead pricing. Experiments were conducted using a hardware-in-the-loop setup where heat pump thermal loads were estimated by building energy computer simulations for a typical single-family apartment located in Madrid. The outdoor section of the heat pump was installing in a climate chamber to apply the outdoor temperature profile for the simulated test days.
DR signals were sent using OpenADR 2.0b requesting different levels of load curtailment. A rule-based controller used the signals to reduce heat pump electric power usage as requested. In addition, a day-ahead price profile was sent and both rule-based and model-predictive controllers were used to modify heat pump operation to minimize customer energy charges while seeking little-to-no impact on occupant comfort. The resulting electrical load profiles were compared to baseline days where no DR events were initiated.
Test results indicated that the load curtailment strategies were effective in achieving the target power limits for both space heating and cooling without a negative impact on comfort, cost or consumption. In addition, the predictive and rule-based price controllers efficiently shifted loads from high demand to low-price periods. The rule-based controller achieved 48% cost savings in heating mode and 58% savings in cooling mode. For the scenarios tested, power rebound effects after completion of the DR event were not significant.
Downloads
Download this paper as pdf: 8-058-21_Amarnath.pdf
Download this presentation as pdf: 8-058-21_Amarnath_pres.pdf
Panels of
1. Energy consumption and wellbeing
2. Policy innovations to ensure, scale and sustain action
3. Policy, finance and governance
4. Monitoring and evaluation for a wise, just and inclusive transition
5. A smart new start for sustainable communities
7. Policies for a green recovery in the buildings sector
8. Buildings: technologies and systems beyond energy efficiency